This guide explains how to connect a hardware SiteManager model 11xx, 15xx, 33xx or 35xx to the Inuatek Data Collection Cloud (DCC), using the SiteManager Data Collection Module (DCM).

You can follow the guide with either a new SiteManager or one already configured for remote access. The first test uses a simulator running in the SiteManager, so you do not need a connected PLC or HMI. Once you can see the simulated data in DCC, you can configure collection from your actual equipment.

The initial configuration can also be reused to provision multiple SiteManagers. Each unit appears as a separate device under the customer company where the configuration was originally created. See Reuse the configuration for fast provisioning.

Prerequisites​

  • A supported hardware SiteManager with firmware release 9.6 or later.
  • A GateManager domain administrator account and access to the SiteManager GUI.
  • The SiteManager is online in a GateManager domain that your account can access.
  • A DCC account with permission to create devices under the intended company.
  • DCM enabled under your Secomea subscription or existing agreement. Secomea's current packages include DCM in Professional and Premium; confirm eligibility with your Secomea provider if you are unsure. See Secomea's DCM introduction.
  • Working NTP time synchronization, configured under System > Time in the SiteManager. Selecting NTP is not sufficient if the SiteManager cannot reach its time server. With the default WaitForNTP=true, DCM waits for synchronization before collecting samples.

Before changing an existing installation, retain a backup of its configuration. See SiteManager backup configuration. If DCM is already in use, also retain its configuration and certificates using the appropriate export or backup functions.

Choose the appropriate setup​

The word New refers to setting up the DCC connection. An existing SiteManager can also be connected, but you must choose whether to retain its agents.

Your situationSetup choiceAdditional action
A new SiteManager without an agent setup you need to retainNew SiteManagerThe downloaded configuration includes the simulator agent setup.
A SiteManager with existing agents used for remote accessNew SiteManager, excluding agentsExisting agents are retained. You must manually associate a suitable DCM agent with the simulator collector.
A SiteManager already using DCM for data collectionReview the existing configuration before importing a new setupBack up and plan how to retain or migrate the existing collection setup. Contact Inuatek if you need help.

Important: The New SiteManager option imports an agent setup and can overwrite existing agents. Choose New SiteManager, excluding agents if you need to retain them. Excluding agents preserves the agents only: the import still deletes the existing DCM configuration and certificates, replacing them with the downloaded setup. Do not use this as a configuration merge for an installation already collecting data.

Step 1: Download the DCM configuration from DCC​

  1. Open IoT Administration in DCC.

  2. Find the company under which the SiteManager should appear in the tree on the left.

  3. Right-click the company and select Create device.

    Open create device menu

  4. Select Secomea SiteManager from the device dropdown.

  5. Select New SiteManager or New SiteManager, excluding agents, according to the table above. Read the instructions and import warning displayed for your choice.

    Select SiteManager setup option

  6. Click Download configuration.

Step 2: Import the configuration into the SiteManager​

  1. Open the GUI of the SiteManager you want to connect.
  2. Go to Maintenance > Import.
  3. Select the downloaded configuration file and complete the import.
  4. Follow the instructions below for your selected setup option.

Option A: New SiteManager​

The imported setup includes the DCM configuration and the agent association needed for the DCCsim simulator. Once the import is applied and the prerequisites are met, DCM starts and sends simulated data to DCC.

Open DCM > Status and check that DCM reaches Normal Operation and that the dataserver has connected. Continue to Step 3.

Option B: New SiteManager, excluding agents​

This import retains your existing agents. The simulator configuration is installed, but its collector must be associated with a DCM agent before it can collect and send samples.

Create Device dialogue showing New SiteManager, excluding agents and the DCM import warning

  1. In the SiteManager GUI, open GateManager > Agents.

  2. Locate a suitable DCM agent. If none exists, create an agent of type Generic / Data Collector Module for this test.

  3. Edit the agent's Device IP & Parameters field. Add the following parameter after the IP address, separated by a space:

    dcmcn=DCCsim

    The field follows this format:

    <IP address> dcmcn=DCCsim

    <IP address> is a placeholder for the agent's address, not text to enter literally. For a dedicated simulator agent, the worked example below uses 127.0.0.1 dcmcn=DCCsim. Retain the address and other required parameters of an existing agent. Use a dedicated simulator agent if an existing agent already serves another collector.

  4. Save the agent configuration.

  5. Open DCM > Status and check that DCM reaches Normal Operation and the dataserver has connected.

DCCsim is the collector name, not the SiteManager's DCM ID. The value after dcmcn= must match the collector name in the DCM configuration exactly. For this example, use DCCsim with the capitalization shown above.

Watch the video walkthrough for the setup excluding agents for a demonstration of this approach.

Step 3: Verify that DCC is receiving data​

  1. Return to IoT Administration in DCC and click Refresh tree.

    Refresh the device tree

  2. Locate the SiteManager under your company. On first connection, the device is normally named using its MAC address.

  3. Open Data Viewer from the DCC menu or top header.

  4. Expand the SiteManager and select the DCCsim collector.

  5. Select the sine-wave data point. Its name may be sine or Sine, depending on the configuration; the worked example below uses Sine. You should see a sine curve with new samples arriving.

    Simulated sine curve in Data Viewer

What this test verifies: The simulator is running and its data reaches DCC. It does not yet verify communication with a PLC, HMI or other connected equipment.

Tip: Right-click the device in the administration tree to give it a meaningful name, such as its appliance name in GateManager. Its MAC address remains available for identification and searching.

Reuse the configuration for fast provisioning​

You do not need to generate a new initial DCC configuration for every SiteManager. Keep the original configuration downloaded for the customer company as a provisioning master and import it into additional SiteManagers. They will register as separate devices under that same company.

For example, a machine builder can keep this configuration on a USB flash drive and use it when preparing SiteManagers for a series of machines. For USB setup, follow Secomea's USB configuration procedure for the supported hardware and required file handling. Importing through Maintenance > Import remains an alternative.

Each unit must also have working network and GateManager settings, as listed in the prerequisites.

What happens on the first connection?​

On first connection, DCC identifies the SiteManager from its GateManager URL and unique device identity, creates its DCM ID, and replaces the initial certificate with a device-specific certificate over the encrypted connection. That certificate is used for subsequent connections and cannot identify another SiteManager. See question 7 in the SiteManager Security FAQ.

Use the original onboarding file for provisioning, rather than a backup containing an already enrolled unit's certificate.

Choose a provisioning master for your installation​

  • Identical machines: Reuse a configuration with the required collectors and agent setup, provided the equipment addresses, protocol settings and sample definitions match each installation.
  • Existing or differing agent setups: Use New SiteManager, excluding agents, then associate the required collectors locally. Adjust each agent's IP address and parameters for its equipment.
  • Different customer companies: Generate a separate onboarding configuration under each intended company. Reusing one company's configuration registers new SiteManagers under that company.

The same import consequences described above apply to every unit. Retaining agents does not retain existing DCM configuration and certificates.

Worked example: Agents and collectors​

An agent specifies the local target and its parameters. The DCM configuration defines the collector's protocol, sample points and processing. The dcmcn= parameter links the agent to the matching CollectorName.

SiteManager agents linked to the DCCsim, Factory and Modbus collectors

Agent name in this exampleDevice IP & ParametersMatching CollectorNameProtocol in the DCM configuration
DCC127.0.0.1 dcmcn=DCCsimDCCsimSimulator
Factory_VPN192.168.82.249 dcmcn=FactoryFactoryOPC-UA/TCP
Modbus192.168.82.249 dcmcn=ModbusModbusModBus/TCP

The IP addresses are examples from this installation; use the addresses of your own equipment.

The first agent is a Generic / Data Collector Module Device that runs the internal sine-wave simulator. The second is an existing ifm electronic / Ethernet agent for an OPC UA-enabled PLC, with DCM enabled and dcmcn=Factory added. The third is a generic DCM agent linked to the Modbus collector. This illustrates that an existing equipment agent can also support data collection; a dedicated generic DCM agent is another option.

The agent names are descriptive labels. For example, the agent called Factory_VPN maps to the collector called Factory, not to a collector called Factory_VPN. Likewise, the name Modbus does not select a protocol: the collector's Protocol field does that.

The corresponding JSON principles​

The configuration has three entries in its Collectors array. This reduced excerpt shows the names, protocols and a selection of sample names:

{
"Collectors": [
{
"CollectorName": "DCCsim",
"Protocol": "Simulator",
"SamplePoints": [{ "SampleName": "Sine" }]
},
{
"CollectorName": "Factory",
"Protocol": "OPC-UA/TCP",
"SamplePoints": [
{ "SampleName": "boolTest1" },
{ "SampleName": "Factory_temp" }
]
},
{
"CollectorName": "Modbus",
"Protocol": "ModBus/TCP",
"SamplePoints": [
{ "SampleName": "Word1" },
{ "SampleName": "Word2" }
]
}
]
}

This is a structural illustration, not an importable configuration. It omits sample data types, addresses, access settings, timing, other samples and the dataserver configuration. Keep the DCC connection settings and certificates generated for your intended customer company.

In the full example:

  • DCCsim generates Sine internally every second, without reading a PLC.
  • Factory reads OPC UA nodes. Each sample defines its node identity, data type and sampling settings; boolTest1 is sampled every 3 seconds and Factory_temp every 60 seconds.
  • Modbus defines register reads in ModbusAccess. Samples refer to a read using FCREF and locate a value within that read using FCOffset. The example also defines calculated, event-triggered samples.
  • DataServers defines how collected data is delivered to DCC. Collection from equipment and delivery to the cloud are separate parts of the configuration.

The supplied test configuration sets WaitForNTP=false; it can therefore collect before NTP synchronizes. Keep time synchronization in your operational setup, and use the default wait behavior unless you have a specific reason to change it.

Worked example: Check the DCM status​

Open DCM > Status after applying the configuration and agent associations.

SiteManager DCM status with three collectors, a DCC dataserver and store-and-forward graphs

Read the page in three parts:

  1. Collector Status: DCCsim, Factory and Modbus each have their own current status. In this screenshot, all three show Normal Operation. If one fails while the others work, investigate that collector's agent mapping, target and protocol settings.
  2. Dataserver Status: The DCC row describes delivery to the cloud, separately from collection. Check this row when collectors run but samples do not reach DCC.
  3. Store and Forward: The incoming and outgoing graphs show collection and delivery rates. The disk section shows buffering usage and capacity; incoming and outgoing byte rates need not match.

Current Status and Last Registered Event describe different things. In this screenshot, the Factory collector shows an older OPC UA MaxStringLength event, Modbus records a successful reconnection, and the DCC dataserver retains an older timeout waiting for an ACK. These are not all current failures; compare each event's timestamp and age with the current status.

The yellow DCM configuration warnings detected banner is also present. Use Details and the logs to investigate the warnings, and confirm that fresh samples arrive in DCC. Green current-status rows alone do not resolve a configuration warning or verify every sample point.

Connectivity and security considerations​

SPD uses an outbound encrypted connection, normally TCP 443, independently of remote access. SiteManager proxy settings do not apply; TLS inspection can disrupt it.

Disable Cloud config updates controls DCC updates to DCM, not agents or network settings. Remote-access blocking through the digital input does not stop telemetry. Optional Web/VNC and write widgets use separate remote-access permissions.

For details, see the SiteManager Security FAQ.

Troubleshooting​

Start in DCM > Status. Use DCM > Status > Details to inspect collectors and dataservers, and Log > View for errors.

SymptomWhat to check
The SiteManager does not appear in DCCConfirm that the file was imported into the intended SiteManager, inspect dataserver status, and refresh the tree under the company selected during setup.
DCCsim is missing or no sine samples arriveCheck the agent association and the exact parameter dcmcn=DCCsim. Confirm the collector exists in the installed configuration and that NTP has synchronized.
The dataserver cannot connectCheck its destination, network access and certificates. Ask IT to investigate firewall, proxy or TLS-inspection restrictions.
DCM is waiting for time synchronizationCheck System > Time, the configured NTP server and its reachability.
Remote access works, but data collection does notCheck the DCM dataserver connection independently of the GateManager connection.
Changes made in DCC are not appliedCheck Disable Cloud config updates and review the configuration-update errors.

See Secomea's SiteManager DCM troubleshooting tools for diagnostic examples.

If the problem persists, contact Inuatek support. Include the SiteManager model, firmware version, MAC address, chosen setup option, and relevant status or error messages. Do not include private keys or passwords.

Next: Collect data from your actual equipment​

After the simulator test succeeds, configure the collectors and sample points needed for your PLCs, HMIs or other equipment. Each collector must be associated with the appropriate SiteManager agent using dcmcn=<collector name>.

Use these references for the next stage:

If you are replacing a failed or existing SiteManager, review GateManager's Replace Appliance procedure before following a new-installation workflow.